AS487L-AL-ST-NF-EXP-SP

Explosion Proof

AS487L-AL-ST-NF-EXP-SP

Air Shower
- Construction of 16 ga unfinished aluminized steel
- OD 60”w x 96”l x 130”h
- ID 47 1/2”wide x 85” long x 90”h
- Top blower box to have (1) 5 HP, TEFC, 460V, 3 phase, direct drive high pressure motor blower,
developing 1800 CFM to 4” SP, vibration isolated (Class II - Div I - Group E,F.G)
- local disconnect switch
- 99.99% gasket seal hepa filter mounted in blower box, (1) 24” x 24” x 12”
- (40) PVC nozzles on walls & ceiling @ 7000 FPM each
- hinged & gasketed doors for motor / blower & filter as shown on drawing
- Externally mounted control system.
- PLC controlled system
- painted steel NEMA 4 enclosure w/ touch screen mounted on enclosure door & regulator for pneumatic door locks & switches
- No floor
- (2) Unit mounted photohelic gauges w/ pilot light alarms for hepa & prefilter
- Unit mounted, rated photo eye sensor for automatic start in rated enclosure
- (1) 36” x 84” Anodized aluminum door at the entrance, clear anodized w/ half ¼” safety glass insert & solid bottom panel,
push/pull hardware, rated door lock & switch, closure, (1) rated door lock **SHIPPED LOOSE** for field installation
on existing customer door to create interlock.
- (2) E-stop switches
- 35% Disposable prefilters in low wall mounted aluminum grilles
- 60 FC surface mounted fluorescent lighting, (Class II - Div I - Group E,F.G)
- (1) Sleeve for sprinkler (head & pipe by others)
- 42 ½” long x 46" wide x 88"high 16 ga, steel channel around the exit door for spacer,
shipped loose in sections for field install
- Unit shipped in (4) pieces - 2 base sections - 1 blower filter module - 1 entry section

NOTES
- All internal wiring in Sealtite w/ fittings-Remote NEMA 4, painted steel enclosure
w/ disconnect for mounting in a safe area out side the unit
- Division I rated pneumatic door locks & door switches
- Division I rated pneumatic emergency stop switches
- Division I rated flush lights

Please Call for Pricing