AS3127

Tunnel

AS3127

- Construction of 16 ga, type 304 SS
- OD 52"w x 144"l x 120"h
- ID 40"w x 140"l x 80"h
- Top blower box to have (2) 5 HP, 480V, 3 phase, 60 HZ, direct drive high pressure motor blower, developing 1800 CFM each to 4" SP, vibration isolated
- 99.99% gasket seal HEPA filter mounted in blower box, filter to be replaceable from the inside of the unit through a hatch in the ceiling
- (72) PVC nozzles on walls & ceiling @ 7000 FPM each
- Hinged & gasketed door for motor & blower on top of blower box
- Internally mounted, Nema 4, painted steel controls enclosure, w/PLC controller mounted on unit
- No floor w/ ceiling mounted sensor for automatic start
- (2) 36" x 80" Anodized aluminum frame doors w/ 1/4" safety glass window, electrically interlocked (magnet locks) w/ (3) E-stops
- 60 FC flush mounted LED lighting
- 35% Disposable prefilters in low wall returns w/ perforated SS grilles
- Unit assembled & tested in the shop prior to shipping

ID 36"w x 144"l x 80"h

Please Call for Pricing